Installation
Electrical installation
24
Lenze · Decentralised frequency inverter 8400 motec (CANopen option) · EDS84DMOTCAN EN 4.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.3 Specification of the bus cable
We recommend to use CAN cables in accordance with ISO 11898-2:
Observe the notes provided on the Bus cable length
( 24)!
5.2.4 Bus cable length
Total cable length
1. Check that the total cable length is not exceeded.
The total cable length is defined by the baud rate.
[5-1] Total cable length
CAN cables according to ISO 11898-2
Cable type Twisted in pairs with shield
Impedance 120 Ω (95 ... 140 Ω)
Cable resistance/cross-section
Cable length 300 m
Cable length 301 ... 1000 m
70 mΩ/m / 0.25... 0.34 mm
2
(AWG22)
40 mΩ/m / 0.5 mm
2
(AWG20)
Signal propagation delay 5 ns/m
Note!
It is absolutely necessary to comply with the permissible cable lengths.
Observe the reduction of the total cable length due to the signal delay of the repeater.
Checking the use of repeaters
( 25)
Mixed operation refers to different nodes being connected to the same network.
If the total cable lengths of the nodes are different at the same baud rate, the smaller
value must be used to determine the maximum cable length.
Baud rate [kbps] Max. bus length [m]
20 4013
50 1575
125 600
250 275
500 113
800 38
1000 13