Commissioning
Possible settings via DIP switch
30
Lenze · Decentralised frequency inverter 8400 motec (CANopen option) · EDS84DMOTCAN EN 4.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Possible settings via DIP switch
[6-1] DIP switch
6.3.1 Setting the baud rate
The baud rate ...
• must be the same for all networked CANopen nodes;
• can be set via the DIP switches a...c or via the »Engineer« (code C00351
).
Settings in the Lenze »Engineer«
( 32)
The DIP switches serve to ...
• Setting the baud rate
( 30) (switches: a ... c)
• Setting the CAN node address
( 31)
(switches: 1 ... 64)
Lenze setting: all switches in OFF position
Note!
• The DIP switches can only be accessed when the drive unit is detached from the
communication unit. Loosen the four fixing screws at the drive unit. Observe the
notes in the mounting instructions.
• Switch off the voltage supply of the inverter and the external supply of the
communication unit before you start disassembling the drive unit.
• The DIP switches are only read in when the device is switched on.
DIP switch position Baud rate
c b a
ON OFF ON 20 kbps
OFF ON ON 50 kbps
OFF ON OFF 125 kbps
OFF OFF ON 250 kbps
OFF OFF OFF 500 kbps
ON ON OFF 800 kbps
ON OFF OFF 1000 kbps