Error messages
Possible causes and remedies
59
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 4.0 - 09/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Slave 1 AS-I ASIC Profile Failure [0x01bc813d]
Slave 2 AS-I ASIC Profile Failure [0x01bc813e]
Response (Lenze setting printed in bold) Setting: C13207/1 / C13208/1 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
• The AS-i profile read by slave 1 (via MCU) does not
correspond to the AS-i profile 7.A.5
• Module-internal switching error
•AS-i ASIC error
• Check voltage supply, wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• If this error continues to occur, please contact the
Lenze service. (it might be necessary to replace the
Communication Unit.)
Response (Lenze setting printed in bold) Setting: C13207/3 / C13208/3 ( adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
• The AS-i profile read by slave 2 (via MCU) does not
correspond to the AS-i profile 7.A.E
• Module-internal switching error
•AS-i ASIC error
• Check voltage supply, wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• If this error continues to occur, please contact the
Lenze service. (it might be necessary to replace the
Communication Unit.)