Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011 L 413
8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
oS1: Maximum speed limit reached [xx.0123.00032]
oS2: Max. motor speed [xx.0123.00033]
Id1: Motor data identification error [xx.0123.00057]
Id3: CINH motor data identification [xx.0123.00058]
Id4: Resistor identification error [xx.0123.00059]
Response (Lenze setting printed in bold) Setting: C00579 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
The device has recognised that the maximum speed has
been reached.
• Limit setpoint selection to maximum values.
• Adjust set speed limitation (C00909
) and frequency
limitation (C00910
) if necessary.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device has recognised that the maximally
permissible motor speed has been reached.
• Limit setpoint selection to the maximally permissible
motor speed.
• If required, adapt set maximum motor speed
(C00965
).
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop : 4: WarningLocked 5: Warning 6: Information
Cause Remedy
During the identification of the motor parameters, an
error has occurred.
Possible causes:
• Interrupted motor cable.
• Switched-off power section during the identification.
• Implausible start parameter settings.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Correct start parameters for the motor parameter
identification (motor nameplate data).
• Stable power supply of the device.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop : 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device has detected controller inhibit during the
motor data identification.
• This cancels the identification process. The Lenze
setting of the motor data is used.
• Do not set controller inhibit during the motor data
identification.
• Do not execute any device function which may
activate controller inhibit.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked : 5: Warning 6: Information
Cause Remedy
The device has recognised that an error has occurred in
the calculation of the motor cable resistance.
• The parameters for cable cross-section and cable
length are implausible.
Enter sensible values for cable cross-section and motor
cable length.