8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
414 L Firmware 11.00 - DMS 8.0 EN - 10/2011
oC12: I2xt overload - brake resistor [xx.0123.00065]
oC11: Clamp operation active [xx.0123.00071]
Id5: Pole position identification error [xx.0123.00074]
oC13: Maximum current for Fch exceeded [xx.0123.00090]
ot2: Speed controller output limited [xx.0123.00093]
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
Too frequent and too long braking processes. Check drive dimensioning.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device indicates that the "CLAMP" overcurrent
limitation has been activated.
A permanent clamp operation causes an overload
disconnection.
Reduce setpoint generation dynamics or motor load.
Response (Lenze setting printed in bold) Setting: C00643/1 (; Adjustable response)
; 0: No Reaction : 1: Fault 2: Trouble ; 3: TroubleQuickStop ; 4: WarningLocked ; 5: Warning ; 6: Information
Cause Remedy
The pole position identification has not been completed
successfully.
Check parameter setting of the pole position
identification.
Response (Lenze setting printed in bold)
0: No Reaction : 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause Remedy
The device has detected a motor current which exceeds
the maximum current limit at permanent switching
frequency of the inverter.
If a permanent switching frequency inverter is set, a
certain limit arises for the maximum current,
depending on the setting. If this current limit is
exceeded due to a load impulse or overload, an error
message is displayed.
Observe the maximum current setting depending on
the set switching frequency of the inverter.
Reduce the required load or setting of the dynamic
switching frequency if necessary.
Response (Lenze setting printed in bold) Setting: C00567 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
The output of the speed controller has reached the
internal limit value. In this state, the speed controller is
not able anymore to correct the system deviation.
Only with "Closed loop" operation or vector control
(SLVC).
Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control