8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
FC01: Switching frequency reduction [xx.0123.00094]
FC02: Maximum speed for Fchop [xx.0123.00095]
oC14: Direct-axis current controller limitation [xx.0123.00096]
oC15: Cross current controller limitation [xx.0123.00097]
oC16: Torque controller limitation [xx.0123.00098]
Response (Lenze setting printed in bold) Setting: C00590 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Load-dependent switching frequency reduction Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
Response (Lenze setting printed in bold) Setting: C00588 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Maximum speed for chopper frequency has been
reached.
The maximum speed has been exceeded depending
on the switching frequency.
Select the correct maximum speed as a function of the
switching frequency.
Motor control: Defining speed limits
Response (Lenze setting printed in bold) Setting: C00570/1 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Direct-axis current controller limitation is active. Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
Response (Lenze setting printed in bold) Setting: C00570/2 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Cross current controller limitation is active. Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).
Motor control
Response (Lenze setting printed in bold) Setting: C00570/3 (; Adjustable response)
: 0: No Reaction ; 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Actuator limitation according to speed controller. Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control