Firmware ≤ 11.00 - DMS 8.0 EN - 10/2011 L 417
8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
An01: AIN1_I < 4 mA [xx.0125.00001]
CE04: MCI communication error [xx.0127.00002]
CE0F: MCI control word [xx.0127.00015]
CE4: CAN bus off [xx.0131.00000]
CA06: CAN CRC error [xx.0131.00006]
Response (Lenze setting printed in bold) Setting: C00598/1 (; Adjustable response)
; 0: No Reaction ; 1: Fault ; 2: Trouble : 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Open-circuit monitoring for analog input 1 has tripped.
• Only if the analog input has been configured as a
current loop of 4 ... 20 (C00034/1
=2).
• Check wiring of the analog X3/A1I input terminal for
open circuit.
• Check minimum current values of the signal sources.
Response (Lenze setting printed in bold) Setting: C01501/1 (; Adjustable response)
: 0: No Reaction ; 1: Fault ; 2: Trouble ; 3: TroubleQuickStop ; 4: WarningLocked ; 5: Warning ; 6: Information
Cause Remedy
Communication error with extension module in slot 1. • Eliminate EMC interference.
• Switch off controller, correctly plug in the module,
switch on the controller again.
• Mains switching or restart of the controller,
respectively.
• Replace module/controller.
• If the problem occurs again, you needs to consult
Lenze.
Response (Lenze setting printed in bold) Setting: C00594/2 (; Adjustable response)
; 0: No Reaction : 1: Fault ; 2: Trouble ; 3: TroubleQuickStop 4: WarningLocked ; 5: Warning 6: Information
Cause Remedy
Bit 14 ("SetFail") of the wMciCtrl control word of the
LS_DriveInterface
system block has been set.
Trace back signal source on the bus (e.g. PROFIBUS) that
sets bit 14 ("SetFail").
Response (Lenze setting printed in bold) Setting: C00592/2 (; Adjustable response)
: 0: No Reaction ; 1: Fault ; 2: Trouble ; 3: TroubleQuickStop ; 4: WarningLocked ; 5: Warning ; 6: Information
Cause Remedy
CAN on board: "Bus off" status
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes have the same ID.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign different IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold) Setting: C00592/1 (; Adjustable response)
: 0: No Reaction ; 1: Fault ; 2: Trouble ; 3: TroubleQuickStop ; 4: WarningLocked ; 5: Warning ; 6: Information
Cause Remedy
CAN on board: A faulty CAN telegram has been detected. • Check wiring and bus terminating resistor.
• Eliminate electrical interference (e.g. EMC).