Controller enable
Depending on the selected operating mode
(Cool)
different
procedures are necessary to enable the controller.
Terminal control,
i.e.
CO01 =
-O-,
-2-,
-4-
l Apply a voltage between 13 and 30V across terminal 28.
l
If
you have pressed the STP key, enable the controller with SH
+ STP in addition.
In
case
of terminal control, CO40 serves as a display:
l CO40
=
-0- means controller is inhibited.
l CO40 =
-l-
means controller is enabled.
Control via keypad, i.e.
CO01
= -l-
*
Apply a voltage between 13 and 30V across terminal 28.
l If you have pressed the STP key, enable the controller with SH
+
STP in addition.
l If you have set CO40 to -0- via the keypad, enter CO40 =
-1-
to
enable the controller as
weil.
Code
Name
Parameter (Factory setting
is
printed in bold)
CO40 Controller
Q
Controller
inhibited/inhibit
enable
-l-
Controller
enabled/enable
Acceptance
SH
+
PRG
Control via LECOM, i.e. CO01 = -3-, -5-, -6-, -7-
*
Apply a voltage between 13 and 30V across terminal 28.
l If you have pressed the STP key, enable the controller with SH
+
STP in addition.
l Send CO40
=
-l-
via the
intetface
which has been selected for
control
3.1.2 Quick stop
/
Select
direction
of rotation
Quick stop
The quick stop function (QSP) serves to decelerate the drive to
standstill as fast as possible. For this, a deceleration time
tan
be
set which is independent of the normally required deceleration
times. It
tan
be set via Cl 05.
Code Name Parameter (Factory setting
is
printed in bold) Acceptance
Cl05
Deceleration
5.0 s 0.00 s
110
ms)
1 .OO
s
ON-LINE
time for quick
1 .o
s
(100 ms) 10.0s
stop
10s
11
SI
100s
100s
UOI
990
s
Quick stop
tan
always be activated via the terminals 21 and 22
(LOW
Signal
at both
terminals),
independently of the selected
operating mode
(Cool).
When switching on the controller a HIGH
Signal
(from terminal 20
or external supply) is applied at terminals
21
and 22 the
dnve
is at
standstill with the function
“QSP”.
In
case
of terminal controi, CO42 serves as a display:
l CO42
=
-O-
means, quick stop is not
active,
l CO42
=
-l-
means, quick stop is
active.
-
-.
-