The
Io
control, also referred to a
“magnetizing-current
control”
allows
a considerabiy
higher
torque compared to the normal
V/f-
characteristic control, without the motor being overexcited when
the drive is deloaded.
3.7.1 V/f-characteristic control
You have to
Change
from
Io
control (factory
setiing)
to
V/f-
characteristic control if you want to supply several drives with
different loads or rated power from one
controller.
Also for pump and
blower drives to be operated with a
Square
characteristic, a
V/f-
characteristic control is required.
V/f
characteristic
With V/f-characteristic control the output voltage is
controlled
according to the characteristic set via CO1 4 and CO1 6.
Via
code
CO14 you
tan
determine whether the characteristic
should have a linear or a
Square
shape.
0
fdN
Linear characteristic
fdN
Square characteristic
-,
70
The
Square
characteristic
tan
be used for pump and blower drives
or
comparable
applications.
hze