With control and programming via keypad or LECOM
interfaces
you
tan
Start
the loading of a Parameter set
under
CO02.
Under
CO02
you
tan
also load the factory setting.
Code Name
Parameter (Factory setting is printed in bold)
Acceptance
CO02 Load
-O-
Factory setting [SH + PRG]
Parameter set
-l-
Parameter set 1
-2-
Parameter set 2
-3-
Parameter
Set
3
-4
Parameter set 4
5.2.10
Reset
I-component
/
D-component
-
dancer-Position controller
In the configurations with dancer-Position controller, you
tan
set the
integral-action component or the differential component to zero via
the assigned input. Please observe the
notes
given on page 81
when assigning the inputs.
5.2.11
Suppression of the dancer-Position controller
The dancer-Position controller
tan
be suppressed via the assigned
input.
If
you want to use the input for overlaying the controller, the
polarity of the input
tan
be inverted by setting Cl 14
=
1. Please
observe the
notes
given on page 81 when assigning the inputs.
5.2.12 Reset of the
Sensor
compensation
The
Sensor
compensation
tan
be reset to zero via the assigned
input. Please observe the
notes
given on page 81 when assigning
the inputs.
5.3
Freely assignable digital Outputs, relay output
Factory setting
Output
Function
Al
Frequency below a certain
level
A2 Maximum
current
reached
A3
Setpoint
reached
A4
no function *
Kll,
Kl4
Relay output: Fault indication
*
Terminal A4 is used as frequency output via
switch
S2 (factoty setting).
If you want to use A4 as freely assignable digital output, remove the
cover
of the
controller and set the
switch
as shown on page 32.
Level
LOW active
HIGH active
HIGH active
LOW active
Contact open
-
Changing the
functions
If you want to assign an output with a function,
which
has not been
assigned yet, proceed as follows:
l Select the output
which
you want to assign
under
code
Cl 16.
l Select the required function
under
code
Cl 17.
l Determine
under
code
Cl 18
whethkr
the
Signal
is activated at
HIGH or LOW.
-