EasyManua.ls Logo

Lenze 9300 Series - Page 149

Lenze 9300 Series
458 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Adjusting the motor
Motor temperature monitoring with PTC or thermal contact
6.6
6.6.3
6.6−9
EDSVF9383V EN 7.1−04/2012
Codes for parameter setting
Code Possible settings IMPORTANT
No. Name Lenze Selection
C0585 MONIT OH8 3
0 TRIP
Configuration of motor
temperature monitoring
l Temperature monitoring via
PTC input (T1, T2)
6.6−8
See System
Manual
(extension)
2 Warning
3 Off
Note!
ƒ In the Lenze setting the motor temperature monitoring is
switched off!
ƒ If you work with several parameter sets, the monitoring must
be activated separately in each parameter set!
1. Connect the monitoring circuit of the motor to T1 and T2.
With 1.6kW < R < 4kW, the monitoring responds.
2. Set the controller reaction:
C0585 = 3: Temperature monitoring of the motor is switched off.
C0585 = 0: TRIP error message (display of keypad: OH8 )
C0585 = 2: Warning signal (display of keypad: OH8 !)
Connect the PTC input with a fixed resistor:
ƒ R>4kW: The fault message OH8 must be activated.
ƒ R<1kW: Fault message must not be activated.
Activation
Function test

Table of Contents

Other manuals for Lenze 9300 Series

Related product manuals