Configuration
Code table
8
8.5
8.5−35
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0582 MONIT OH4 2
2 Warning
Configuration monitoring OH4,
heatsink temperature
l The operating temperature can
be set in C0122
See System
Manual
(extension)
3 Off
C0583 MONIT OH3 3
0 TRIP
Configuration of motor
temperature monitoring with
fixed operating temperature
l Only for KTY at X8
l The operating temperature is
fixed at 150 °C
6.6−10
See System
Manual
(extension)
2 Warning
3 Off
C0584 MONIT OH7 3
2 Warning
Configuration of monitoring
motor temperature with variable
operating temperature
l Only for KTY at X8
l When reaching the
temperature set in C0121 the
warning OH7 is activated
6.6−10
See System
Manual
(extension)
3 Off
C0585 MONIT OH8 3
0 TRIP
Configuration of motor
temperature monitoring
l Temperature monitoring via
PTC input (T1, T2)
6.6−8
See System
Manual
(extension)
2 Warning
3 Off
C0587 MONIT SD3 3
0 TRIP
Configuration of monitoring SD3,
encoder at X9
l Monitors the voltage supply at
X9/pin 8
See System
Manual
(extension)
2 Warning
3 Off
C0588 MONIT
H10/H11
0
0 TRIP
Configuration of monitoring H10
and H11, thermal sensors in the
controller
l H10: Sensor error − heatsink
temperature
l H11: Sensor error − interior
temperature
See System
Manual
(extension)
3 Off
C0591 MONIT CE1 3
0 TRIP
Configuration of monitoring CE1,
communication error at CAN−IN1
See System
Manual
(extension)
2 Warning
3 Off
C0592 MONIT CE2 3
0 TRIP
Configuration of monitoring CE2,
communication error at CAN−IN2
2 Warning
3 Off
C0593 MONIT CE3 3
0 TRIP
Configuration of monitoring CE3,
communication error at CAN−IN3
2 Warning
3 Off
C0594 MONIT SD6 3
0 TRIP
Activation of the motor
temperature monitoring with KTY
at X8
l Use C0594 = 0 or 2 to activate
monitoring
l In case of a short circuit or
interruption at X8/5 and X8/8
the fault message SD6 is
activated
l Configuration of the response
when exceeding the motor
temperature
Fixed operating temperature
in C0583
Variable operating
temperature in C0584
6.6−10
See System
Manual
(extension)
2 Warning
3 Off