Configuration
Code table
8
8.5
8.5−56
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0879
Resetting control words
l C0879 = 1 performs one reset
1 Reset C135 0 0 Ready
2 Reset AIF 0
1 Reset
3 Reset CAN 0
C0880
Selection list 2
Configuration of digital input
signals, function block DCTRL
l Select parameter set
l Selection of a parameter set via
binary coding of the digital
input signals
See System
Manual
(extension)
1 CFG: PAR*1 1000 FIXED0 C0880/1 C0880/2 Selected
parameter set
2 CFG: PAR*2 1000 FIXED0
0 0 Parameter set 1
0 1 Parameter set 2
1 0 Parameter set 3
1 1 Parameter set 4
C0881
CFG: PAR−LOAD 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block DCTRL
l LOW−HIGH edge = Load
selected parameter set into
C0880
See System
Manual
(extension)
C0884
Function block DCTRL
l Display of the signals linked in
C0880 and C0881
See System
Manual
(extension)
1 DIS: PAR*1
2 DIS: PAR*2
3 DIS: PAR−LOAD
C0885
CFG: R 51 DIGIN1 Selection list 2
Configuration of digital input
signals, function block R/L/Q
l Truth table:
Inputs Outputs
R L R/L QSP
0 0 0/1 1
1000
0110
11˘˘
˘ State is unchanged
See System
Manual
(extension)
C0886
CFG: L 52 DIGIN2 Selection list 2
C0889 0 1
Function block R/L/Q
l Display of the signals linked in
C0885 and C0886
1 DIS: R
2 DIS: L
C0890
CFG: N−SET 5050 NSET−NOUT Selection list 1 Configuration of analog input
signal, function block MCTRL
l Speed setpoint
8.2−25
8.2−40
C0891
CFG: M−Add 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block MCTRL
l Additional torque setpoint or
torque setpoint
8.2−40
C0892
CFG: Lo−M−LIM 5700 ANEG1−OUT Selection list 1 Configuration of analog input
signal, function block MCTRL
l Lower torque limit in [%] of
C0057
C0893
CFG: HI−M−LIM 19523 FCODE−472/3 Selection list 1 Configuration of analog input
signal, function block MCTRL
l Upper torque limit in [%] of
C0057
C0898
CFG: M−LIM
switch
0
0 M−LIM ON Reduced torque
limit is active
Torque limitation in the field
weakening range, function block
MCTRL
l If the torque limit is reduced,
the maximum possible torque
in the field weakening range is
lowered with 1/f. This provides
a higher motor stability in the
field weakening range
8.2−40
1 M−LIM OFF Reduced torque
limit is inactive