EasyManua.ls Logo

Lenze 9300 Series - 3.5 Rated data (devices in 400 V design)

Lenze 9300 Series
458 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Rated data (devices in 400V design)
3
3.5
3.5−1
EDSVF9383V EN 4.0−11/2007
3.5 Rated data (devices in 400V design)
Basis of the data
Voltage Frequency
Supply
3/PE AC 400 V [U
N
] 340 V − 0 % ... 456 V + 0 % 45 Hz − 0 % ... 65 Hz + 0 %
DC (alternatively) [U
DC
] Not possible
Output voltage [U
OUT
] 3 ~ 0 ... U
N
0 ... 300 Hz
9300 Mains current
1)
Typical motor power
ASM (4−pole)
Power loss
Type I
r
[A] P
N
[kW] P
N
[hp] P
V
[kW]
EVF9335−EV
EVF9335−EVVxxx
2)
200 110
150 2.8
EVF9336−EV
EVF9336−EVVxxx
2)
238 132 200 3.3
EVF9337−EV
EVF9337−EVVxxx
2)
285 160 250 4.0
EVF9338−EV
EVF9338−EVVxxx
2)
356 200 300 5.0
EVF9381−EV
EVF9381−EVVxxx
2)
475 250 350 6.6
EVF9382−EV
EVF9382−EVVxxx
2)
570 315 450 8.0
EVF9383−EV
EVF9384−EVVxxx
2)
713 400 550 10.0
The currents for EVF9381 ... EVF9383 are to be considered as total currents of master and slave
1)
For a controller switching frequency of 2 kHz
2)
Device in variant V030, V060 or V110
9300 Output currents
Rated current Maximum current
2)
1 kHz
1)
2 kHz
1)
4 kHz
1)
1 kHz
1)
2 kHz
1)
4 kHz
1)
Type I
N1
[A] I
N2
[A] I
N4
[A] I
M1
[A] I
M2
[A] I
M4
[A]
EVF9335−EV
EVF9335−EVVxxx
3)
210 210 210 315 315 315
EVF9336−EV
EVF9336−EVVxxx
3)
250 250 250 375 375 375
EVF9337−EV
EVF9337−EVVxxx
3)
300 300 270 450 450 405
EVF9338−EV
EVF9338−EVVxxx
3)
375 375 330 560 560 495
EVF9381−EV
EVF9381−EVVxxx
3)
500 500 500 750 750 750
EVF9382−EV
EVF9382−EVVxxx
3)
600 600 540 900 900 810
EVF9383−EV
EVF9384−EVVxxx
3)
750 750 660 1125 1125 990
The currents for EVF9381 ... EVF9383 are to be considered as total currents of master and slave
Bold print = Lenze setting
1)
Switching frequency of the inverter
2)
The currents apply to a periodic load change with an overcurrent time of 1 minute at a maximum
and a base load time of 2 minutes with maximally 75 % I
Nx
3)
Device in variant V030, V060 or V110

Table of Contents

Other manuals for Lenze 9300 Series