Basics for wiring according to EMC
Motor cable
5.3
5.3.3
5.3−2
EDSVF9383V EN 7.1−04/2012
5.3.3 Motor cable
ƒ Use only shielded motor cables with braid made of tinned or
nickel−plated copper. Shields made of steel braid are not suitable.
The overlap rate of the braid must be at least 70 % with an overlap
angle of 90 °.
ƒ The cables used must meet the requirements of the application (e.g.
EN 60204−1).
ƒ The cable for the motor temperature monitoring (PTC or thermal
contact) must be shielded and separated from the motor cable.
With Lenze system cables, the cable for the motor temperature
monitoring is integrated into the motor cable.
ƒ Always place the shield of the motor cable at both sides − at the drive
controller and at the motor.
Always connect the shields to the conductive and grounded
mounting plate with a surface as large as possible.
ƒ The motor cable is perfectly installed if
it is routed separately of mains cables and control cables,
crosses mains cables and control cables only at a right angle,
is not interrupted.
ƒ If it is inevitable to have an interruption (e.g. through chokes,
contactors or terminals):
The unshielded cable must not be longer than 100 mm (depending
on the cable cross−section).
Chokes, contactors, terminals, etc. must be separated from other
components (min. distance = 100 mm).
The motor cable shield must be connected to the mounting plate
with a surface as large as possible directly before and after the point
of interruption.
ƒ Connect the shield in the motor terminal box or at the motor housing
to PE with a surface as large as possible.
Metal cable glands at the motor terminal box ensure that the shield
is connected to the motor housing with a surface as large as possible.