Basic devices in the power range 110 ... 200 kW
Motor connection
5.4
5.4.7
5.4−7
EDSVF9383V EN 7.1−04/2012
5.4.7 Motor connection
ƒ To comply with the EMC regulations, Lenze recommends to use
shielded motor cables.
ƒ Shield clamps are not included in the scope of supply.
Stop!
The user is responsible for sufficient strain relief!
BR2BR1
PE
UVW
40 mm
PE
15-20 Nm
M6
133-176 lb-in
U, V, W
25-30 Nm
M8
221-264 lb-in
0
max.
300 mm
1
9300VEC005
Fig. 5.4−6 Motor connection example
BR1, BR2 Brake resistors can only be operated with variants V060, V110, V270
and V300
Connect the motor cable shield with a surface as large as possible to
the control cabinet mounting plate by using the clamps.
Conductive surface
Ensure to have the poles right!
Do not exceed the maximum motor cable length!
9300 vector Installation in accordance with EN 60204−1
U, V, W PE
Type [mm
2
] [mm
2
]
EVF9335−EV
EVF9335−EVVxxx
150
2 × 50
1)
95
EVF9336−EV
EVF9336−EVVxxx
150
2 × 50
1)
95
EVF9337−EV
EVF9337−EVVxxx
150
2 × 50
1)
95
EVF9338−EV
EVF9338−EVVxxx
240
2 × 95
1)
150
1)
Two conductors per path; both conductors must have the same
cross−section
Observe the national and regional legislation
Cable cross−section