EasyManua.ls Logo

Lenze 9300 Series - Page 197

Lenze 9300 Series
328 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
Standard devices in the power range 55 ... 75 kW
Motor connection
5
197
EDKVS9332X DE/EN/FR 8.0
T1
T2
PE
U
VW
2
3
0
1
U, V, W,
PE
M8
15 Nm
132 lb-in
}
+
PE
M5x12
3 Nm (26.5 lb-in)
9300vec124
Fig. 5−24 Motor connection with KTY thermal sensor
PE stud
PE cable connection with ring cable lug
U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 240 mm
2
with ring cable lug
Shield clamps
Place shields of motor cable with large surface on the shield sheet and fasten with shield
clamps and M5 × 12 mm screws
Cable ties
Strain relief of motor cable

Table of Contents