Technische Daten
Bemessungsdaten
Betrieb bei 400 V
3
29
EDKVS9332X DE/EN/FR 8.0
9300 Ausgangsströme
8 kHz
1)
16 kHz
1)
Bemessungs-
strom
Maximaler
Strom
2)
Stillstandsstrom Bemessungs-
strom
Maximaler
Strom
2)
Stillstandsstrom
Typ I
N8
[A] I
M8
[A] I
08
[A] I
N16
[A] I
M16
[A] I
016
[A]
EVS9321−xx 1,5 2,25 2,3 1,1 1,65 1,7
EVS9322−xx 2,5 3,75 3,8 1,8 2,7 2,7
EVS9323−xx 3,9 5,85 5,9 2,9 4,35 4,4
EVS9324−xx 7,0 10,5 10,5 5,2 7,8 7,8
EVS9325−xx 13,0 19,5 19,5 9,7 14,6 14,6
EVS9326−xx 23,5 35,3 23,5 15,3 23,0 15,3
EVS9327−xx 32,0 48,0 32,0 20,8 31,2 20,8
EVS9328−xx 47,0 70,5 47,0 30,6 45,9 30,6
EVS9329−xx 59,0 88,5 52,0 38,0 57,0 33,0
EVS9330−xx 89,0 133,5 80,0 58,0 87,0 45,0
EVS9331−xx 110 165 110 70,0 105 70,0
EVS9332−xx 145 217,5 126 90,0 135 72,0
Fettdruck = Lenze−Einstellung
1)
Schaltfrequenz des Wechselrichters
2)
Die Ströme gelten für ein periodisches Lastwechselspiel mit maximal 1 Minute Überstromdauer und 2 Minuten
Grundlastdauer mit maximal 75 % I
N