Configuration
Code table
8
8.5
8.5−4
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0018 fchop 6 Switching frequency of the
inverter
l General rule: The lower the
switching frequency the
lower the power loss
higher the noise
generation
better the concentricity
factor
l Observe derating indications
for high switching
frequencies
l The max. output frequency
(f
max
) is:
fchop = 4 kHz Þ
f
max
= 300 Hz
fchop = 2 kHz Þ
f
max
= 150 Hz
fchop = 1 kHz Þ
f
max
= 150 Hz
6.9−1
1 1 kHz sin loss−optimised
2 2 kHz sin concentricity−optimi
sed
3 4 kHz f_top power−optimised
4 4 kHz sin noise−optimised
6 4/2 kHz sin noise/concentricity−
optimised with
automatic
change−over to low
switching frequency
C0019 Thresh nact=0 0 −36000 {1 rpm} 36000 Operating threshold − automatic
DC injection brake (Auto−GSB)
l Falling below the threshold
in C0019 activates automatic
DC injection braking when
the holding time set under
C0107 > 0
8.2−25
8.2−40
C0020 turn value 100 0 {1 %} 200 Influence on concentricity factor
l Manual influence on the
concentricity factor of the
motor
C0021 slipcomp à −20.00 {0.01 %} 20.00 Slip compensation
à Change of C0086, C0087 or
C0089 sets C0021 to the
calculated rated slip of the
motor
l When changing over to the
vector control mode, C0021 is
set to 0
6.11−1
8.2−25
8.2−40
C0022 Imax current à 0 {0.1 A} I
max
limit in motor mode
à depending on C0086
6.6−15
C0023 Imax gen. à 0 {0.1 A} I
max
limit in generator mode
à depending on C0086
6.6−15
C0025
Feedback type 1
Speed feedback
6.7−1
1 no feedback No feedback
100 IT (C420) − X8 Input of the number
of increments in
C0420
Incremental encoder at X8
l Incremental encoders with
TTL level can only be
connected to X8.
101 IT (C420) − X9 Input of the number
of increments in
C0420
Incremental encoder at X9
l Connect incremental
encoders with HTL−level on
X9 only
Number of
increments:
Incremental encoder at X8
l Incremental encoders with
TTL level can only be
connected to X8.
110 IT512−5V 512 inc
111 IT1024−5V 1024 inc
112 IT2048−5V 2048 inc
113 IT4096−5V 4096 inc