Configuration
Code table
8
8.5
8.5−64
EDSVF9383V EN 4.0−03/2006
IMPORTANTPossible settingsCode
SelectionLenzeNameNo.
C0988 Input signals −199.99 {0.01 %} 199.99
Function block MFAIL
l Display of the signals linked
in C0970, C0973, C0974,
C0975, C0976, C0977 and
C0978
See System
Manual
(extension)
1 DIS: N−SET
2 DIS: ADAPT
3 DIS: CONST
4 DIS:
THRESHLD
5 DIS: NACT
6 DIS: SET
7 DIS: DC−SET
C0989 0 1
Function block MFAIL
l Display of the signals linked
in C0971 and C0972
1 DIS: FAULT
2 DIS: RESET
C1000 DIVISION 1 0 {1} 31
Part factor, function block
CONVPHA1
l Calculate output signal:
See System
Manual
(extension)
OUT[%] + IN[%] @
100%
2
14
@ 2
C1000
C1001
CFG: IN 1000 FIXED0INC Selection list 3 Configuration of input signal,
function block CONVPHA1
C1002 DIS: IN −2147483648 {1} 2147483647 Function block CONVPHA1
l Display of the signal linked in
C1001
C1040 Acceleration 100.000 0.001 {0.001 } 5000.000 Acceleration, function block
SRFG1
l Max. acceleration
See System
Manual
(extension)
C1041 Jerk 0.200 0.001 {0.001 s} 999.999 Jerk, function block SRFG1
l S−ramp time
C1042
CFG: IN 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block SRFG1
C1043
CFG: SET 1000 FIXED0% Selection list 1 Configuration of analog input
signal, function block SRFG1
l Starting value for the ramp
function generator
l Starting value is accepted
when SRFG1−LOAD = HIGH
C1044
CFG: LOAD 1000 FIXED0 Selection list 2 Configuration of digital input
signal, function block SRFG1
l HIGH = accepts the value at
SRFG1−SET and outputs it to
SRFG1−OUT. SRFG1−DIFF
remains on 0 %
C1045 −199.99 {0.01 %} 199.99
Function block SRFG1
l Display of the signals linked
in C1042 and C1043
1 DIS: IN
2 DIS: SET
C1046 DIS: LOAD 0 1 Function block SRFG1
l Display of the signal linked in
C1044
efesotomasyon.com - Lenze