DC−bus operation
Mains chokes for DC−bus operation
10
10.3
10.3−1
EDSVF9383V EN 6.0−11/2009
10.3 Mains chokes for DC−bus operation
Note!
In DC−bus operation mains chokes in front of every input module
are a basic precondition for trouble−free operation.
Mains chokes specified for the input modules in DC−bus operation:
Controller Mains choke
Type Rated mains current Rated current Inductance Order No.
[A] [A] [mH]
EVx9335 200 200 0.14 ELN3−0014H200
EVx9336 238 270 0.11 ELN3−0011H270
EVx9337 285 300 0.09 ELN3−0009H300
EVx9338 356 370 0.09 ELN3−0009H370
EVx9381 475 2 × 270 2 × 0.11 2 × ELN3−0011H270
EVx9382 570 2 × 300 2 × 0.09 2 × ELN3−0009H300
EVx9383 713 2 × 370 2 × 0.09 2 × ELN3−0009H370