Configuration
7-329
L
EDSVS9332P-D22 EN 3.0
Code ImportantPossible settings
No. SelectionLenzeLCD
[C0117] → → Selection list 2 DIGOUT
Signal configuration
Æ
depending on C0005
1 DIGOUT1 30012 pos- ref-ok X5/A1
2 DIGOUT2 30013 POS-IN-TARGET X5/A2
3 DIGOUT3 500 DCTRL- RDY X5/A3
4 DIGOUT4 30101 pos-pfo1 X5/A4
C0118
0
1
HIGH active
LOW active
DIGOUT
Terminal polarity
1 DIGOUT1 POL 0 X5/A1
2 DIGOUT2 POL 0 X5/A2
3 DIGOUT3 POL 0 X5/A3
4 DIGOUT4 POL 0 X5/A4
C0121 OH7 LIMIT 150 45 {1 °C} 150 Temperature for OH7
Warning threshold - motor temperature
C0122 OH4 LIMIT 85 45 {1 °C} 85 Temperature for OH4
Warning threshold - heatsink temperature
C0125 BAUD RATE 0 0
1
2
3
4
9600 baud
4800 baud
2400 baud
1200 baud
19200 baud
LECOM baud rate
LECOM baud rate for 2102 module
C0126 MONIT CE0 3 0
2
3
Trip
Warning
Off
Conf. CE0
Configuration communica tion error monitoring
with automation interface CE0
C0130 ACT TI
0
0
1
2
...
14
15
C0012/C0013 active
T
ir
1/T
if
1active
T
ir
2/T
if
2active
...
T
ir
14/T
if
14 active
T
ir
15/T
if
15 active
NSET
Active T
i
times of NSET
C0134 RFG CHARAC 0 0
1
linear
S-shaped
NSET RFG characteristic
Characteristic of ramp function generator for
main setpoint
C0135 CONTROL WORD 0 0 {1} 65535 Control word
Controller control word for LECOM-A/B/LI or
operating module.
C0136
0
1 CTRLWORD C135 Control word in DCTRL
2 CTRLWORD CAN ControlwordinCAN-IN
3 CTRLWORD AIF ControlwordinAIF-IN
C0141 FCODE (SETVAL) 0.0 -199.9 {0.1} 199.9 Main setpoint
Freely assignable code for relative analog
signals
•
used as main setpoint in the configurations
C0005 = xxx1
C0142 START OPTIONS 1 0
1
Start lock
Autostart
Start option
Start condition is executed:
•
after mains connection
•
after message (t > 0.5s)
•
after TRIP
C0150 STATUS WORD
0
0 {1} 65535 Status word
when linked with automation interfaces
•
binary interpretation indicates the bit states
C0151 FDO (DW)
0
Display (hex.) of the free di gital output signals
configured with C0116
•
binary interpretation indicates the bit states