Configuration
7-361
L
EDSVS9332P-D22 EN 3.0
Code ImportantPossible settings
No. SelectionLenzeLCD
C1213 REF. MODE 0 0
1
2
3
4
5
6
7
8
9
10
11
+home
-home
+LIM,-home
-LIM,+home
+MARK,-home
-MARK,+home
+MARK,+TP
-MARK,-TP
+TP
-TP
+LIM,-TP
-LIM,+TP
Homing mode
•
Mode for homing (valid for manual mode
and program homing).
C1214 REF TP-INPUT 4 1
2
3
4
TP-IN = X5/E1
TP-IN = X5/E2
TP-IN = X5/E3
TP-IN = X5/E4
Homing touch probe
•
Selection o f the touch probe input terminal
for homing acc. to modes 6...9. When using
an incremental enc oder, the TP i nput X5/E4
is particularly suitable.
C1215
0 +slope TP input edge
1 TP-TRANS 0
1
-slope
•
Selection of the edge for the touch probe
... ... ...
inpu
erminals. (
pplies
o homing acc.
o
4 TP-TRANS 0
mo
es
...
,
pos
on
ng,
s
orage
C1216 V-REF2 ACTIVE. 0 0
1
inactive
active
Activating 2nd homing speed
C1218 0 {0.0001 units} 214000
Following error tolerance
1 FOL.TOLERANCE 4.0000
2 FOL.TOLERANCE 1.0000
C1220
0
-214000 {0.0001 units} 214000
1 POS-TARGET Actual target position
2 POS-SETPOS Actual position setpoint
3 POS-ACTPOS Actual position
4 ACT.FOLLOW ERR Actual following error
5 ACTPOS ABS. Read in absolute value
6 REFMARK 0-IMP Distance of REF-MARK to index pulse
7 ACT.HOME OFFS Actual reference dimension offset
8 ACT.HOME POS. Actual home position
9 ACT. WAY Path still to be positioned
10 ACT. C1223
Real internal values of the codes C1223, C1224,
11 ACT. C1224
C1240, C1250
12 ACT. C1240
(in
ernal limi
a
ion possible: see chap
er
“
”
13 ACT. C1250
rou
es
oo
ng,
au
n
ca
on
14 ACT. VNORM
Internal value for fault analysis
15 ACT. ANORM