Installation
4-20
L
EDSVS9332P-B EN 3.0
Max. permissible cable cross-sections and screw tightening torques:
Max. permissible cable
cross-sections
Screw-tightening torques
Type
U, V, W, PE T1, T2 U, V, W PE connection
Shield/
Strain relief
T1, T2
9321 ... 9326 4mm
2
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb-in)
3.4 Nm
(30 lb-in)
9327 ... 9329 25 mm
2
1.5 mm
2
5 Nm (44 lb-in)
M4: 1.7 Nm (15 lb-in)
0.5 ... 0.6 Nm
9330 ... 9331 95 mm
2
.
15 Nm (132 lb-in)
M5: 3.4 Nm (30 lb-in) (4.4...5.3 lb-in)
9332 120 mm
2
30 Nm (264 lb-in)
Cable cross-sections Connection with Note
Up to 4 mm
2
Wire end ferrules
Up to 6 mm
2
Pin-end connectors
>25 mm
2
Ring cable lugs The cable cross-section is only limited by the cable bushing in the housing.
Max. permissible motor cable length:
a
r
= 400 V (+10%) a
r
= 480 V (+10%)
Type f
chop
=8kHz f
chop
=16kHz f
chop
=8kHz f
chop
=16kHz
max. permissible motor cable length max. permissible motor cable length
9321, 9322 up to 50 m up to 45 m up to 50 m up to 25 m
9323 ... 9332 up to 50 m up to 50 m up to 50 m up to 50 m
Tip!
•
Switching on the motor side of the controller is only permitted for safety switch-off
(emergency switch-off).
•
The max. permissible motor cable length of types 9323 - 9332 will be reduced if the motor
cablehasmorethanasinglecore.
– Two parallel single cores: l
max
=17m
– Three parallel single cores: l
max
=9m