Installation
4-23
L
EDSVS9332P-B EN 3.0
Central supply with supply module
•
When connecting the supply module, the corresponding Operating Instructions must be
observed.
L 3
N
P E
L 1
L 2
L 1 L 2 L 3
9 3 4 1 - 9 3 4 3
P E
+ U G - U G
K 1
U
V
W
M
3 ~
P E
L 1 L 2
L 3
9 3 2 X - 9 3 3 X
P E
+ U G - U G
P E
U
V
W
M
3 ~
P E
L 1
L 2
L 3
9 3 2 X - 9 3 3 X
P E
+ U G - U G
P E
F 4 F 5
F 6 F 7
F 8 F 9
Z 2
F 1
Z 1
F 2 F 3
F 1
Z 1
F 2 F 3
K35.0114
Fig. 4-14 Central supply for DC-bus connection of several drives
Z1 Mains supply filter
Z2 Supply module
F1...F6 Protection, see “ Cable protection” ( E 3-6)/ “Mains connection” ( E 4-13)
F4...F9 DC bus fuse; fuse holder with / without alarm contact, see “Cable protection” ( E 3-6)/ “Mains
connection” ( E 4-13)
K1 Main contactor
Tip!
If the power supply of the supply module is not sufficient, a parallel supply can be installed via the
mains supply input of a controller (see Manual, Part F). In this case, the controllers can only be
operated with the assigned mains filters.