Commissioning
5-10
L
EDSVS9332P-C EN 3.0
5.6.4 Parameters for manual control
Stop!
Check the parameters for manual control. In order to check a configuration select small values for
acceleration and deceleration (e. g. default setting).
The default setting of the parameters is sufficient for most of the application cases. Enter the setting
as follows:
Fig. 5-6 Menu ” Manual control” in the parameter menu
Step
Command Function
1 Select ”Basic settings” dialog box.
2 Cl i ck on ”Parameter menu” button. Open parameter menu
3 Click on ”Positioning functions” menu. Open ”Positioning functions” menu.
4 Click on ”Manual control” menu. Open ”Manual c ontrol” menu.
5 Click on C1243. Enter a new value. Manual control speed. Default setting:
5 % of vmax
6 Click on C1252. Enter a new value. Manual c ontrol acceleration. Default setting:
10 % of amax
7 Click on C0003. Save settings
8 Click on ”Dialog control” menu. Open ”Control” dialog box.