Appendix
Code table
14−28
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0240
(A)
Process controller
output inversion
(PCTRL1−INV−ON)
(parameter
channel)
0 0 Not inverted
Set digital signal PCTRL1−INV−ON (process
controller output inversion) via keypad/PC or
parameter channel
1 Inverted
C0241
(A)
Process controller
not hidden/hidden
(PCTRL1−FADING)
(parameter
channel)
0 0 Process controller unhiding
Set digital signal PCTRL1−FADING (process
controller hiding/unhiding) via keypad/PC or
parameter channel
1 Process controller hiding
C0242
(A)
Activation of
process controller
inverse control
0 0 Normal control Act. value increases ð Output frequency
increases
1 Inverse control Act. value increases ð Output frequency
decreases
C0243
(A)
Deactivation of
additional setpoint
(PCTRL1−NADD−OF
F) (parameter
channel)
0 0 PCTRL1−NADD active
Set digital signal PCTRL1−NADD−OFF
(deactivation of additional setpoint) via
keypad/PC or parameter channel
1 PCTRL1−NADD not active
C0244
(A)
Root function actual
process controller
value
0 0 not active
1
|PCTRL1−ACT|
Internal calculation
1. Storing sign of PCTRL1−ACT
2. Extraction of the root of the absolute
value
3. Multiply the result with the sign
C0245*
(A)
Comparison value
for MSET1=MACT
0 0 MCTRL1−MSET (C0412/6 or C0047)
Selection of a comparison value for setting
the digital output signal MSET1=MACT
(torque threshold 1 = actual torque value)
If the difference between
MCTRL1−MSET1 and MCTRL1−MACT or
C0250 is within C0252:
MSET1=MACT = HIGH after time set
under C0254
1 Value under C0250