Appendix
Code table
14−31
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0311*
Functions for
special applications
2
1
0 Functions are switched off By entering the sum of the selected values
you can activate a combination of the
functions.
(C0156 as of
software 3.1,
C0056 as of
software 3.5)
1
Selection:
Reference value for the current
threshold C0156
Display value in C0056
Function is active: Function is switched off:
In the operating mode V/f characteristic control In the operating mode V/f characteristic
control:
C0156: Rated controller current C0156: Rated controller current
C0056: Controller load (MCTRL−MOUT) C0056: Controller load (MCTRL−MOUT)
In the operating mode vector control or
sensorless torque control:
In the operating mode vector control or
sensorless torque control: Rated motor
torque
C0156: Rated controller current C0156: Rated motor torque
C0056: Controller load (MCTRL−MOUT) C0056: Actual torque value
(MCTRL-MACT)
(As of software
version 3.1)
2
Effect of the S−shaped ramp
Function is active: Function is switched off:
The S−shaped ramp (C0182) has no effect on the
quick stop ramp (C0105).
The S−shaped ramp (C0182) has also an
effect on quick stop.
(As of software
version 3.5)
4
Selection of the flying restart function
Function is active: Function is switched off:
Flying restart function optimised for two−pole
motors is active
Standard flying restart function is active
C0320
(A)
Actual process
controller value
(PCTRL1−ACT)
−650.00 {0.02 Hz} 650.00 Only display
C0321
(A)
Process controller
setpoint
(PCTRL1−SET)
−650.00 {0.02 Hz} 650.00 Only display
C0322
(A)
Process controller
output without
precontrol
(PCTRL1−OUT)
−650.00 {0.02 Hz} 650.00 Only display
C0323
(A)
Ramp function
generator input
(NSET1−RFG1−IN)
−650.00 {0.02 Hz} 650.00 Only display
C0324
(A)
Ramp function
generator output
(NSET1−NOUT)
−650.00 {0.02 Hz} 650.00 Only display
C0325
(A)
PID controller
output
(PCTRL1−PID−OUT)
−650.00 {0.02 Hz} 650.00 Only display
C0326
(A)
Process controller
output
(PCTRL1−NOUT)
−650.00 {0.02 Hz} 650.00 Only display
C0350*
System bus node
address
1 1 {1} 63 Only for the E82ZAFCC system bus
function module on the FIF interface.
Changes will become effective after the
command "reset node"
During operation with 217x
communication modules the node
address must be set under C0009.