Function library
FCODE (free codes)
12
310
EDBCSXS064 EN 4.0
Codes
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0017 FCODE (Qmin) 50
Free code for using speed signals
(Speed signal FCODE_nC17_a)
309
−16000 {1 rpm} 16000
C0037 Set−value rpm 0
Setpoint selection in rpm
(FCODE_nC37_a)
309
−16000 {1 rpm} 16000
C0108 Gain for relative analog signals
(AOUT)
309
1 FCODE(gain) 100.0 −199.99 {0.01 %} 199.99 FCODE_nC108_1_a
2 FCODE(gain) 100.0 FCODE_nC108_2_a
C0109 Offset for relative analog signals
(AOUT)
309
1 FCODE(offset) 0.0 −199.99 {0.01 %} 199.99 FCODE_nC109_1_a
2 FCODE(offset) 0.0 FCODE_nC109_2_a
C0135 Control word 0
System control word DCTRL
0 {1} 65535 Controller evaluates information
as 16 bits (binary−coded)
Bit 0 Not assigned
Bit 1 Not assigned
Bit 2 Not assigned
Bit 3 Quick stop (QSP)
Bit 4 Not assigned
Bit 5 Not assigned
Bit 6 Not assigned
Bit 7 Not assigned
Bit 8 Operation inhibit (DISABLE)
Bit 9 Controller inhibit (CINH)
Bit 10 TRIP−SET
Bit 11 TRIP−RESET
Bit 12 Not assigned
Bit 13 Not assigned
Bit 14 Not assigned
Bit 15 Not assigned
C0141 FCODE(setval) 0.0
Main setpoint (FCODE_C141_a)
309
−199.99 {0.01 %} 199.99
C0250 FCODE 1 Bit 0
Freely selectable digital signal
(1 bit)
309
0 1
C0470 Freely configurable code for
digital signals
Hexadecimal value is bit−coded.
309
1 FCODE 8bit 0 00 {hex} FF C0470/1 = C0471, bit 0 ... 7
2 FCODE 8bit 0 C0470/2 = C0471, bit 8 ... 15
3 FCODE 8bit 0 C0470/3 = C0471, bit 16 ... 23
4 FCODE 8bit 0 C0470/4 = C0471, bit 24 ... 31