Function library
Torque (torque control)
Setpoint processing
12
352
EDBCSXS064 EN 4.0
12.28.3.3 Influencing the ramp function generator
ƒ If the controller is inhibited, the ramp function generator accepts the actual speed
and passes it to the downstream function. This function has priority over all other
functions.
ƒ If the input TORQUE−NSET.RfgStop = TRUE (C7511/8), the ramp function generator is
stopped. Changes of the input of the ramp function generator have no effect on the
output signal.
ƒ If the input TORQUE−NSET.Rfg0 = TRUE (C7511/3) the ramp function generator
reaches zero along the deceleration ramp.
ƒ The threshold in C0241 specifies when the message "Setpoint reached" is output.
On the ramp function generator for the torque setpoint, the following applies: input
signal = output signal
Code Possible settings IMPORTANT
No. Designation Lenze/
{Appl.}
Selection
C0241 NSET RFG I = O 1.00
Threshold for message "Setpoint
reached"
On the ramp function generator
for
l speed setpoint (for "speed
control")
l torque setpoint (for "torque
control")
input signal = output signal.
329
352
0.00 {0.01 %} 100.00 100 % = n
max