EasyManua.ls Logo

Lenze I/O system 1000 - Page 537

Lenze I/O system 1000
583 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 PROFINET communication
9.8 Parameterising the counter
537
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter data
Data set Name Description/value Lenze
No. Byte
0x01 0 Input frequency
Counter 1, track A
Filters for instance serve to filter signal peaks in the case of
an unclean input signal.
0 (0x00): 500 kHz
1 (0x01): 300 kHz
2 (0x02): 100 kHz
3 (0x03): 60 kHz
4 (0x04): 30 kHz
6 (0x06): 10 kHz
7 (0x07): 5 kHz
8 (0x08): 2 kHz
9 (0x09): 1 kHz
Other values are not permissible!
0x02
1 Input frequency
Counter 1, track B
0x02
2 Input frequency
Counter 2, track A
0x02
3 Input frequency
Counter 2, track B
0x02
0x80 0 Counting direction
counter 1, track B
Bit 2 ... 0: Reserved
Bit 3: Invert counting direction track B
0 = no (do not invert)
1 = yes (invert)
Bit 7 ... 4: Reserved
0x00
1 Signal evaluation
counter 1
Bit 2 ... 0: Signal evaluation
0b000 = counter deactivated (the other parameter data
details for the counter are ignored)
0b001 = rotary transducer 1-fold (connection to "A/pulse"
input)
0b010 = rotary transducer 2-fold (connection to "A/pulse"
input)
0b011 = rotary transducer 4-fold (connection to "A/pulse"
input and "B/direction")
0b100 = direction (pulse at "A/pulse" input and direction
at "B/direction" input)
Bit 7 ... 3: Reserved
0x00
0x82 0 Counting direction
counter 2, track B
Bit 2 ... 0: Reserved
Bit 3: Invert counting direction track B
0 = no (do not invert)
1 = yes (invert)
Bit 7 ... 4: Reserved
0x00
1 Signal evaluation
counter 2
Bit 2 ... 0: Signal evaluation
0b000 = counter deactivated (the other parameter data
details for the counter are ignored)
0b001 = rotary transducer 1-fold (connection to "A/pulse"
input)
0b010 = rotary transducer 2-fold (connection to "A/pulse"
input)
0b011 = rotary transducer 4-fold (connection to "A/pulse"
input and "B/direction")
0b100 = direction (pulse at "A/pulse" input and direction
at "B/direction" input)
Bit 7 ... 3: Reserved
0x00