9 PROFINET communication
9.11 Parameterising technology modules
555
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Option 4 / 5, TMO
0x80 5 TMO (HIGH byte) TMO serves to define the maximally permissible interval
between two frames.
0 ... 65535 [ms] (0x0000 ... 0xFFFF)
0x00
6 TMO (LOW byte) 0xFA
Option 6, number of start identifiers
0x80 7 Number of start
identifiers
0x00: 1 start identifier (2. start identifier is ignored)
0x01: 2 start identifiers
0x01
Option 7, start identifier 1
0x80 8 Start identifier 1 ASCII value of the initial character that is sent in advance of
a frame and marks the start of a transmission.
0 ... 255 (0x00 ... 0xFF)
0x00
Option 8, start identifier 2
0x80 9 Start identifier 2 ASCII value of the initial character that is sent in advance of
a frame and marks the start of a transmission.
0x00
Option 9, number of end identifiers
0x80 10 Number of end
identifiers
0x00: 1 end identifier (2. end identifier (0x310D/x) is
ignored)
0x01: 2 end identifiers
0x00
Option 10, end identifier 1
0x80 11 End identifier 1 ASCII value of the end character that is sent after a frame and
marks the end of a transmission.
0 ... 255 (0x00 ... 0xFF)
0x00
Option 11, end identifier 2
0x80 12 End identifier 2 ASCII value of the end character that is sent after a frame and
marks the end of a transmission.
0 ... 255 (0x00 ... 0xFF)
0x00
Option 12, reserved
0x80 13 Reserved 0x00
Data set Name Description/value Lenze
No. Byte