Error code Error message Error type Congurable in
30346 0x768A Memory module: wrong type Fault -
30352 0x7690 EPM
rmware version incompable Fault -
30353 0x7691 EPM data: rmware type incompable Fault -
30354 0x7692 EPM data: new rmware type detected Fault -
30355 0x7693 EPM data: PU size incompable Fault -
30356 0x7694 EPM data: new PU size detected Fault -
30357 0x7695 Invalid parameter changeover conguraon Warning -
30358 0x7696 EPM data: unknown parameter found Informaon -
30359 0x7697 Parameter changes lost Fault -
33045 0x8115 Time-out (PAM) No response 0x2552:004
33050 0x811A BACnet me-out Fault 0x2856:001
33154 0x8182 CAN: bus o Trouble 0x2857:010
33155 0x8183 CAN: warning Warning 0x2857:011
33156 0x8184 CAN: heartbeat me-out consumer 1 Fault 0x2857:005
33157 0x8185 CAN: heartbeat me-out consumer 2 Fault 0x2857:006
33158 0x8186 CAN: heartbeat me-out consumer 3 Fault 0x2857:007
33159 0x8187 CAN: heartbeat me-out consumer 4 Fault 0x2857:008
33185 0x81A1 Modbus: network me-out Fault 0x2858:001
33186 0x81A2 Modbus: incorrect request by master Warning -
33425 0x8291 CAN: RPDO1 me-out Fault 0x2857:001
33426 0x8292 CAN: RPDO2 me-out Fault 0x2857:002
33427 0x8293 CAN: RPDO3 me-out Fault 0x2857:003
33553 0x8311 Torque limit reached No response 0x2D67:001 (P329.01)
33664 0x8380 Funcon not allowed in selected operang mode Warning -
36992 0x9080 Keypad removed Fault -
65285 0xFF05 Safe Torque O
is locked Fault -
65286 0xFF06 Motor overspeed Fault 0x2D44:002 (P350.02)
65289 0xFF09 Motor phase missing No response 0x2D45:001 (P310.01)
65290 0xFF0A Motor phase failure phase U No response 0x2D45:001 (P310.01)
65291 0xFF0B Motor phase failure phase V No response 0x2D45:001 (P310.01)
65292 0xFF0C Motor phase failure phase W No response 0x2D45:001 (P310.01)
65305 0xFF19 Motor parameter idencaon fault Fault -
65311 0xFF1F FMF Error Fault -
65335 0xFF37 Automac start disabled Fault -
65336 0xFF38 Load loss detected No response 0x4006:003 (P710.03)
65337 0xFF39 Motor overload No response 0x4007:003
65366 0xFF56 Maximum motor frequency reached Warning -
65393 0xFF71 Wrong password Warning -
65394 0xFF72 Warning Warning -
65395 0xFF73 Fatal Error Fault -
65413 0xFF85 Keypad full control acve Warning -
8784 0x2250 CiA:
Connuous over current (internal) Keypad display: PU over current
Cause Remedy Error type/response
•
Connuous overcurrent on the inverter/
mot
or side.
•
Overcurrent at the brake chopper (brake
transistor).
•
DC bus relay has not been closed due to a
malfuncon.
•
Connuous overcurrent on the inverter/
motor side.
•
DC bus relay has not been closed due to a
malfuncon.
•
Check mot
or and wiring for short circuits.
•
Check brake resistor and wiring.
•
Check motor switching.
•
Check
sengs of the motor data.
•
Check motor and wiring for short circuits.
Fault
•
The inverter is disabled immediately. The
motor has no torque (coasts).
•
The error can only be reset aer a blocking
me.
Blocking me: 5 s
Diagnoscs and fault eliminaon
Error codes, causes and remedies