Fusing data
Inverter i550-C0.25/230-2 i550-C0.37/230-2 i550-C0.55/230-2 i550-C0.75/230-2
Cable installaon in compliance
with
US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
without mains choke
Circuit breaker
Characteriscs -
Max. rated current A 15 15 15 15
Type of fusing Standard
SCCR: requirement Standard short-circuit strength
SCCR: max. short circuit cur-
rent
kA 5 5 5 5
SCCR: voltage 240 Volts Maximum
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 15 15 15
Type of fusing Standard
SCCR: requirement Standard short-circuit strength
SCCR: max. short circuit cur-
rent
kA 5 5 5 5
SCCR: voltage 240 Volts Maximum
with mains choke
Circuit breaker
Characteriscs -
Max. rated current A 15 15 15 15
Type of fusing Standard
SCCR: requirement Standard short-circuit strength
SCCR: max. short circuit cur-
rent
kA 5 5 5 5
SCCR: voltage 240 Volts Maximum
Fuse
Characteriscs all acc. to UL 248 / Class CC
Max. rated current A 15 15 15 15
Type of fusing Standard
SCCR: requirement Standard short-circuit strength
SCCR: max. short circuit cur-
rent
kA 5 5 5 5
SCCR: voltage 240 Volts Maximum
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B
Technical data
3-phase mains connecon 230/240 V
Fusing data
105