Mains connecon 3-phase, 400 V/480 V
Inverter i550-C7.5/400-3 i550-C15/400-3 i550-C30/400-3 i550-C55/400-3
i550-C11/400-3 i550-C18/400-3 i550-C37/400-3 i550-C75/400-3
i550-C22/400-3 i550-C45/400-3
Without RFI lter
Without EMC cat-
egory
Thermal limitaon
Max. motor cable
length shielded
m 100 100 100 100
Max. motor cable
length unshielded
m 200 200 200 200
With integrated RFI lter
Category C1 Max. motor cable
length shielded
m - - - -
Category C2 m 20 20 20 20
Earth-leakage circuit
breaker
mA 300 300 300 300
RFI lter Low Leakage
Category C1 Max. motor cable
length shielded
m - - - -
Earth-leakage circuit
breaker
mA - - - -
RFI lter Short Distance
Category C1 Max. motor cable
length shielded
m 25 - - -
Category C2 m 50 - - -
Earth-leakage circuit
breaker
mA 30 - - -
RFI lter Long Distance from 22 kW: Mains lter
Category C1 Max. motor cable
length shielded
m 50 50 50 50
Category C2 m 100 50 50 50
Earth-leakage circuit
breaker
mA 300 300 300 300
Short Distance
Inverter RFI lter
Order code Dimensions (h x b x t) Weight
mm kg
i550-C0.37/400-3
I0FAE175F100S0000S 276 x 60 x 50 0.9i550-C0.55/400-3
i550-C0.75/400-3
i550-C1.1/400-3
I0FAE222F100S0000S 346 x 60 x 50 1.1
i550-C1.5/400-3
i550-C2.2/400-3
i550-C3.0/400-3
I0FAE255F100S0000S 346 x 90 x 60 2.1
i550-C4.0/400-3
i550-C5.5/400-3
i550-C7.5/400-3
I0FAE311F100S0000S 371 x 120 x 60 2.4
i550-C11/400-3
Technical data
3-phase mains connecon 400 V
RFI lters / Mains lters
135