Inverter i550-C11/400-3 i550-C15/400-3 i550-C18/400-3 i550-C22/400-3
Rated power kW P
N
15 18.5 22 30
Rated power hp P
N
20 25 30 40
Mains voltage range 3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-400/480 V
Rated mains current
without mains choke A I
r, AC
- 48 - -
with mains choke A I
r, AC
27.1 36 43 55
Apparent output power kVA A
ON
19 26 32 38
Rated output current
2 kHz A I
OUT
28.2 38.4 48 56.4
4 kHz A I
OUT
28.2 38.4 48 56.4
8 kHz A I
OUT
- - - -
16 kHz A I
OUT
- - - -
Power loss
2 kHz W 290 404 501 585
4 kHz W 309 430 533 623
8 kHz W - - - -
16 kHz W - - - -
at inverter disablecontroller
inhibit
W 6 18 18 18
Overcurrent cycle 180 s
Max. output current A I
max, out
35 48 60 71
Overload me s t
ol
60 60 60 60
Recovery me s t
re
120 120 120 120
Max. output current during the
recovery me
A 17.6 24 30 35
Overcurrent cycle 15 s
Max. output current A I
max, out
47 64 80 94
Overload me s t
ol
3 3 3 3
Recovery me s t
re
12 12 12 12
Max. output current during the
recovery me
A 17.6 24 30 35
Cyclic mains switching 3 mes per minute
Brake chopper
Max. output current A I
max, 1
29 43 52 52
Min. brake resistance Ω R
min
27 18 15 15
Max. motor cable length shielded
without EMC category m 100 100 100 100
Category C1 (2 kHz, 4 kHz, 8
kHz)
m - - - -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 20 20 20
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 50 35 35 35
Weight kg 3.7 10.3 10.3 10.3
Weight lb 8 23 23 23
Technical data
3-phase mains connecon 400 V "Light Duty"
Rated data
139