Inverter i550-C0.55/230-1 i550-C0.55/230-2 i550-C0.75/230-1 i550-C0.75/230-2
Rated power kW P
N
0.55 0.55 0.75 0.75
Rated power hp P
N
0.75 0.75 1 1
Mains voltage range 1/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0-230/240 V
Rated mains current
without mains choke A I
r, AC
7.6 7.6 10 10
with mains choke A I
r, AC
7.1 7.1 8.8 8.8
Apparent output power kVA A
ON
1.2 1.2 1.6 1.6
Rated output current
2 kHz A I
OUT
3.2 3.2 4.2 4.2
4 kHz A I
OUT
3.2 3.2 4.2 4.2
8 kHz A I
OUT
3.2 3.2 4.2 4.2
16 kHz A I
OUT
2.1 2.1 2.8 2.8
Power loss
2 kHz W 22 22 27 27
4 kHz W 23 23 29 29
8 kHz W 25 25 33 33
16 kHz W 30 30 38 38
at inverter disablecontroller
inhibit
W 6 6 6 6
Overcurrent cycle 180 s
Max. output current A I
max, out
4.8 4.8 6.3 6.3
Overload me s t
ol
60 60 60 60
Recovery me s t
re
120 120 120 120
Max. output current during the
recovery me
A 2.4 2.4 3.2 3.2
Overcurrent cycle 15 s
Max. output current A I
max, out
6.4 6.4 8.4 8.4
Overload me s t
ol
3 3 3 3
Recovery me s t
re
12 12 12 12
Max. output current during the
recovery me
A 2.4 2.4 3.2 3.2
Cyclic mains switching 3 mes per minute
Brake chopper
Max. output current A I
max, 1
3.9 3.9 3.9 3.9
Min. brake resistance Ω R
min
100 100 100 100
Max. motor cable length shielded
without EMC category m 50 50 50 50
Category C1 (2 kHz, 4 kHz, 8
kHz)
m 3 - 3 -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 20 - 20 -
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 50 - 50 -
Weight kg 1 1 1 1
Weight lb 2.2 2.2 2.2 2.2
Technical data
1-phase mains connecon 230/240 V
Rated data
84