PROFIBUS
The network must be terminated with a resistor at the physically rst and last node.
Acvate the bus terminang resistor at these nodes in the bus connecon plug.
Typical topologies
Line with repeater
M
R
1
S1n
S12S11
2
X1
S21
S2n
R
R R
R
M Master X Repeater
S Slave R Acvated bus terminang resistor
Sub D socket 9-pin - X226
View Pin Assignment Descripon
1
6
5
9
5
1
9 6
1 Shield Addional shield connecon
2 n.c.
3 RxD/TxD-P Data line-B (received data/transmied data +)
4 RTS Request To Send (received data/transmied data, no dierenal signal)
5 M5V2 Reference potenal (bus terminang resistor -)
6 P5V2 5 V DC / 30 mA (bus terminang resistor +, OLM, OLP)
7 n.c.
8 RxD/TxD-N Data line-A (received
data/transmied data -)
9 n.c.
Basic network sengs
Use the DIP switch to set the
staon address.
The baud rate is detected automacally.
Address
O
N
32
16 8
4
64
2 1
PROFIBUS
PROFIBUS staon address
64 32 16 8 4 2 1
OFF OFF OFF OFF OFF OFF OFF
Value from parameter
Staon address - example:
OFF OFF ON OFF ON ON ON
Staon address = 16 + 4 + 2 + 1 = 23
Do not set staon address = 126 and staon address = 127. These staon addresses are invalid.
Bold print = de
fault seng
Electrical
installaon
Networks
PROFIBUS