Display code Short designaon Default seng Seng range Address Category
└ P414.01 Frequency 0.0 Hz 0.0 ... 599.0 Hz 0x4004:001 general
└ P414.02 PID value 0.00 PID unit -300.00 ... 300.00 PID unit 0x4004:002 general
└ P414.03 Torque 0.0 % 0.0 ... 1000.0 % 0x4004:003 general
P415.xx HTL inp. seng
└ P415.01 Min.frequency 0.0 Hz -100000.0 ... 100000.0 Hz 0x2640:001 general
└ P415.02 Max. frequency 0.0 Hz -100000.0 ... 100000.0 Hz 0x2640:002 general
└ P415.03 Min.motor.freq 0.0 Hz -1000.0 ... 1000.0 Hz 0x2640:003 general
└ P415.04 Max.motor.freq Device for 50-Hz mains:
50.0 Hz
Device for 60-Hz mains:
60.0 Hz
-1000.0 ... 1000.0 Hz 0x2640:004 general
└ P415.05 Min.PID setpoint 0.00 PID unit -300.00 ... 300.00 PID unit 0x2640:005 general
└ P415.06 Max.PID setpoint 100.00 PID unit -300.00 ... 300.00 PID unit 0x2640:006 general
└ P415.07 Min.torque setp. 0.0 % -400.0 ... 400.0 % 0x2640:007 general
└ P415.08 Max.torque setp 100.0 % -400.0 ... 400.0 % 0x2640:008 general
└ P415.09 Filter me 10 ms 0 ... 10000 ms 0x2640:009 general
P416.xx HTL inp. monit.
└ P416.01 Min.freq.thresh. 0.0 Hz -214748364.8 ...
214748364.7 Hz
0x2641:001 general
└ P416.02 Min.delay thres. 5.0 s 0.0 ... 300.0 s 0x2641:002 general
└ P416.03 Max.freq.thresh. 0.0 Hz -214748364.8 ...
214748364.7 Hz
0x2641:003 general
└ P416.04 Max.delay thres. 5.0 s 0.0 ... 300.0 s 0x2641:004 general
└ P416.05 Monit. condion < min. frequency [1] Selecon list 0x2641:005 general
└ P416.06 Error response No response [0] Selecon list 0x2641:006 general
P420.xx Dig.out.funcon
└ P420.01 Relay funcon Rdy for operat. [51] Selecon list 0x2634:001 general
└ P420.02 DO1 funcon Release brake [115] Selecon list 0x2634:002 general
└ P420.03 DO2 funcon Fault [56] Selecon list 0x2634:003 Appl. I/O
└ P420.10 NetWordOUT1.00 Rdy for operat. [51] Selecon list 0x2634:010 general
└ P420.11 NetWordOUT1.01 Not connected [0] Selecon list 0x2634:011 general
└ P420.12 NetWordOUT1.02 Operat. enabled [52] Selecon list 0x2634:012 general
└ P420.13 NetWordOUT1.03 Fault [56] Selecon list 0x2634:013 general
└ P420.14 NetWordOUT1.04 Not connected [0] Selecon list 0x2634:014 general
└ P420.15 NetWordOUT1.05 Quick stop [54] Selecon list 0x2634:015 general
└ P420.16 NetWordOUT1.06 Running [50] Selecon list 0x2634:016 general
└ P420.17 NetWordOUT1.07 Device warning [58] Selecon list 0x2634:017 general
└ P420.18 NetWordOUT1.08 Not connected [0] Selecon list 0x2634:018 general
└ P420.19 NetWordOUT1.09 Not connected [0] Selecon list 0x2634:019 general
└ P420.20 NetWordOUT1.10 Speed - setp=act [72] Selecon list 0x2634:020 general
└ P420.21 NetWordOUT1.11 At current limit [78] Selecon list 0x2634:021 general
└ P420.22 NetWordOUT1.12 Actual speed=0 [71] Selecon list 0x2634:022 general
└ P420.23 NetWordOUT1.13 Rot.dir.reversed [69] Selecon list 0x2634:023 general
└ P420.24 NetWordOUT1.14 Release brake [115] Selecon list 0x2634:024 general
└ P420.25 NetWordOUT1.15 Inv.dis.safety [55] Selecon list 0x2634:025 general
P421.xx DO inversion
└ P421.01 Relay inverted Not inverted [0] Selecon list 0x2635:001 general
└ P421.02 DO1 inversion Not inverted [0] Selecon list 0x2635:002 general
└ P421.03 DO2 inversion Not inverted [0] Selecon list 0x2635:003 Appl. I/O
P423.xx DO1 freq. setup
└ P423.01 Min. frequency 0.0 Hz 0.0 ... 10000.0 Hz 0x2644:001 general
└ P423.02 Max. frequency 10000.0 Hz 0.0 ... 10000.0 Hz 0x2644:002 general
└ P423.03 Funcon Not connected [0] Selecon list 0x2644:003 general
└ P423.04 Min. signal 0 -2147483648 ... 2147483647 0x2644:004 general
└ P423.05 Max. signal 1000 -2147483648 ... 2147483647 0x2644:005 general
* Default seng depending on the size.
Using accessories
Keypad
Keypad parameterisaon mode
565