Display code Short designaon Default seng Seng range Address Category
P590.xx NetWordINx
P590.01 NetWordIN1 0x0000 0x0000 ... 0xFFFF 0x4008:001 general
P590.02 NetWordIN2 0x0000 0x0000 ... 0xFFFF 0x4008:002 general
P590.03 NetWordIN3 0.0 % 0.0 ... 100.0 % 0x4008:003 general
P590.04 NetWordIN4 0.0 % 0.0 ... 100.0 % 0x4008:004 general
P590.05 NetWordIN5 0.0 % -100.0 ... 100.0 % 0x4008:005 general
P591.xx NetWordOUTx
P591.01 NetWordOUT1 - - (Read only) 0x400A:001 general
P591.02 NetWordOUT2 - - (Read only) 0x400A:002 general
P592.xx Process data IN
P592.01 AC control word 0x0000 0x0000 ... 0xFFFF 0x400B:001 general
P592.02 LECOM ctrl word 0x0000 0x0000 ... 0xFFFF 0x400B:002 general
P592.03 Net.freq. 0.1 0.0 Hz 0.0 ... 599.0 Hz 0x400B:003 general
P592.04 Net.setp. speed 0 rpm 0 ... 50000 rpm 0x400B:004 general
P592.05 Net.freq. 0.01 0.00 Hz 0.00 ... 599.00 Hz 0x400B:005 general
P592.06 Veloc. mode setp 0.0 Hz -599.0 ... 599.0 Hz 0x400B:006 general
P592.07 PID setpoint 0.00 PID unit -300.00 ... 300.00 PID unit 0x400B:007 general
P592.08 Torque mode setp 0 Nm -32768 ... 32767 Nm 0x400B:008 general
P592.09 Torque scaling 0 -128 ... 127 0x400B:009 general
P592.11 PID feedback 0.00 PID unit -300.00 ... 300.00 PID unit 0x400B:011 general
P592.12 NetSereq0.02Hz 0 Hz -29950 ... 29950 Hz 0x400B:012 general
P592.13 N.FrqSet+/-16384 0 -16384 ... 16384 0x400B:013 general
P593.xx Process data OUT
P593.01 AC status word - - (Read only) 0x400C:001 general
P593.02 LECOM stat. word - - (Read only) 0x400C:002 general
P593.03 Frequency (0.1) x.x Hz - (Read only) 0x400C:003 general
P593.04 Motor speed x rpm - (Read only) 0x400C:004 general
P593.05 Drive status - - (Read only) 0x400C:005 general
P593.06 Frequency 0.01 x.xx Hz - (Read only) 0x400C:006 general
P593.07 Torque scaled - - (Read only) 0x400C:007 general
P593.08 Frequency 0.02Hz Hz - (Read only) 0x400C:008 general
P593.09 Freq. [+/-16384] - - (Read only) 0x400C:009 general
P595.xx PAM monitoring
P595.02 Keep alive reg. 0 0 ... 65535 0x2552:002 general
P595.03 Time-out me 10.0 s 0.0 ... 6553.5 s 0x2552:003 general
P595.04 Reacon No response [0] Selecon list 0x2552:004 general
P595.05 Acon No acon [0] Selecon list 0x2552:005 general
P595.06 PAM status - - (Read only) 0x2552:006 general
P595.07 WLAN reset t.out 0 s 0 ... 65535 s 0x2552:007 general
P600.xx PID setup
P600.01 Operang mode Inhibited [0] Selecon list 0x4020:001 general
P600.02 PID process var. Analog input 1 [1] Selecon list 0x4020:002 general
P600.03 PID speed range 100 % 0 ... 100 % 0x4020:003 general
P600.04 PID line speed w/o speed.add. [0] Selecon list 0x4020:004 general
P600.05 Min speed lim -100.0 % -100.0 ... 100.0 % 0x4020:005 general
P600.06 Max speed lim 100.0 % -100.0 ... 100.0 % 0x4020:006 general
P601.00 PID P-component 5.0 % 0.0 ... 1000.0 % 0x4048 general
P602.00 PID I- component 400 ms 10 ... 6000 ms 0x4049 general
P603.00 PID D-component 0.0 s 0.0 ... 20.0 s 0x404A general
P604.00 PID setp.ramp 20.0 s 0.0 ... 100.0 s 0x404B general
P605.xx PID setp. limit
P605.01 Minimum setpoint -300.00 PID unit -300.00 ... 300.00 PID unit 0x404E:001 general
P605.02 Maximum setpoint 300.00 PID unit -300.00 ... 300.00 PID unit 0x404E:002 general
P606.xx PID speed op.
* Default seng depending on the size.