Terminal data
Rated power P
rated
kW 0.37 ... 2.2
Connecon descripon Mains connecon
Connecon X100
Connecon type Non-pluggable
Max. cable cross-secon mm² 4
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 1.2 x 8.0
Rated power P
rated
kW 0.37 ... 2.2
Connecon descripon PE connecon
Connecon PE
Max. cable cross-secon mm² 6
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 2
Tightening torque lb-in 18
Required tool T20
Rated power P
rated
kW 0.37 ... 2.2
Connecon descripon Motor connecon
Connecon X105
Connecon type Non-pluggable
Max. cable cross-secon mm² 4
Max. cable cross-secon AWG 10
Stripping length mm 10
Stripping length in 0.4
Tightening torque Nm 0.5
Tightening torque lb-in 4.4
Required tool 1.2 x 8.0
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V
140