1-phase mains connecon 230/240 V
Rated data
The output currents apply to these operang condions:
•
At switching frequency 2 kHz or 4 kHz: Ambient temperature max. 45 °C (113 °F).
•
At switching frequency 8 kHz, 12 kHz or 16 kHz: Ambient temperature max. 40 °C (104 °F).
Inverter I55AP
137B 137D 155B 155D 175B 175D 211B 211D
Rated power P
rated
kW 0.37 0.55 0.75 1.1
Rated power P
rated
HP 0.5 0.75 1 1.5
Mains voltage range 1/PE AC 170 V ... 264 V, 45 Hz ... 65 Hz
Output voltage 3 AC 0 - 230/240 V
Rated mains current
without mains choke A 5.7 7.6 10 14.3
with mains choke A -
Apparent output power kVA 0.9 1.2 1.6 2.3
Rated output current
2 kHz A 2.4 3.2 4.2 6
4 kHz A 2.4 3.2 4.2 6
8 kHz A 2.4 3.2 4.2 6
12 kHz A 2.2 2.9 3.8 5.4
16 kHz A 1.6 2.1 2.8 4
Power loss
2 kHz W 19 24 30 38
4 kHz W 20 25 32 40
8 kHz W 24 31 40 51
12 kHz W 23 30 38 54
16 kHz W 22 28 35 49
Cyclic mains switching 3 mes per minute
Max. motor cable length
shielded
without EMC category m 50
Category C1 (2 kHz, 4 kHz,
8kHz)
m -
Category C2 (2 kHz, 4 kHz, 8
kHz)
m 10 - 10 - 10 - 10 -
Category C3 (2 kHz, 4 kHz, 8
kHz)
m 35 - 35 - 35 - 35 -
Max. motor cable length
unshielded
without EMC category m 60 80
Degree of protecon
EN IP66 IP31 IP66 IP31 IP66 IP31 IP66 IP31 IP66
NEMA Type
4X
Type
1
Type 4X Type
1
Type 4X Type
1
Type 4X Type
1
Type
4X
Weight m kg 1.8 1.6 1.7 1.8 1.6 1.7 1.8 1.6 1.7 2.7 2.5 2.6
Weight m lb 4 3.5 3.7 4 3.5 3.7 4 3.5 3.7 6 5.5 5.7
Technical data
1-phase mains connecon 230/240 V
Rated data
179