Fusing and terminal data
Inverter i550-C4.0/230-3 i550-C5.5/230-3
Cable installaon in compliance with EN 60204-1
Laying system C
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 32 32
Circuit breaker
Characteriscs B
Max. rated current A 32 32
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 32 32
Circuit breaker
Characteriscs B
Max. rated current A 32 32
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Mains connecon
Connecon X100
Connecon type Screw terminal
Min. cable cross-secon mm² 1.5
Max. cable cross-secon mm² 6
Stripping length mm 9
Tightening torque Nm 0.5
Required tool 0.6 x 3.5
Motor connecon
Connecon X105
Connecon type Screw terminal
Min. cable cross-secon mm² 1.5
Max. cable cross-secon mm² 6
Stripping length mm 9
Tightening torque Nm 0.5
Required tool 0.6 x 3.5
Technical data
3-phase mains connecon 230/240 V
Fusing and t
erminal data
48