Safe homing (SHom)
Safety funcons based on ab
solute posions require an absolute reference point to calculate
and monitor the posion. This reference point is dened via the reference run.
The home posion is the absolute reference point for these safety funcons:
•
Safely-limited posion (SLP) ^ 135
•
Posion-dependent safe speed (PDSS) ^ 136
•
Safe cam (SCA) ^ 141
During the reference run, the drive moves exclusively at a safely limited speed that can be
parameterized (SLS1 ... SLS4). When the reference posion is traversed, the parameterized
posion value is adopted as the "Home Posion".
By parameterizaon it can be set whether the current posion is stored non-volalely when
the voltage supply is switched o. If the restart condions are fullled aer the voltage supply
is switched on again and aer a minimum movement (minireference run), no new reference
run is performed.
4Mini-homing ^ 140
DANGER!
When switched o
, the motor posion must not be changed by external forces.
A change in motor posion will result in injury or even death.
▶
Make sure that the motor posion does not change.
NOTICE
Undetected local change of the home posion.
An unr
ecognized local change of the home posion leads to incorrect values of the absolute
posion.
▶
Mount the components for detecng the reference posion mechanically so that the home
posion cannot change due to external inuences.
Funconal sa
fety
Safety funcons
Safe homing (SHom)
138