Motor holding brake c
onnecon
The inverter is designed for 24 V brakes. A motor holding brake is connected to X106 and
supplied via X107.
DANGER!
Loss of the safe isolaon
Sa
fe isolaon of the control card from the mains potenal is deacvated when the motor and
motor holding brake are connected via a system cable AND X5 and X107 are supplied by a
common power supply unit. This also applies when using a SELV/PELV power supply unit.
Possible consequences: Electric shock in the event of a fault.
▶
Supply X107 and X5 by separate SELV/PELV power supply units if the motor and motor
holding brake are connected via a system cable.
X107 and X5 can be supplied by a common SELV/PELV power supply unit if the
mot
or and motor holding brake are connected via safely isolated installed
cables.
When the motor holding brake is open, a slight knocking sound can be noced
in the mot
or. This stems from test pulses for monitoring the motor brake
control.
Funcons f
or controlling motor holding brakes:
•
Recognion of the brakes
•
Default seng of motor torque
•
Manual mode
•
Automac mode
•
Logical inversion
M 3~
bk
1
bk
2
bk
3
wh
+DSL
bl
-DSL
gnye
EYP008xxxxxxM1xA00
M 3~
bk
1
bk
2
bk
3
wh
+DSL
bl
-DSL
EYP008xxxxxxM1xA00
X109B
T1
T2
X105B
U
V
W
bk
5
+
bk
6
-
BD2
BD1
X106B
gnye
PE
(X109A)
X109
T2
T1
(X105A)
X105
U
V
W
PE
µC
µC
GB
24B
DC 24 V SELV/PELV
(+19.2 V ... +28.8 V)
X107
bk
5
+
bk
6
-
-
+
BD2
BD1
X106A
X106
I75AExxxF
AV00x S1 Q0
I75AExxxF AV00xQQS2
Fig. 11: Connecon diagram for motor holding brake - i750 OCT/PTC version
Electrical ins
tallaon
Motor holding brake connecon