Power supply modules
Rated data (devices for 400/500V mains)
Fuses and cable cross-sections
6
226
EDS94SPP101 EN 7.1
Operation without external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c d L1, L2, L3 - Laying system e L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E94APNE0104 C16 - 2,5 2,5 15 14 300
E94APNE0364 C40 - 10 10 40 8 300
E94APNE1004 - 125 - 50
F: 50
100 1/0 300
E94APNE2454 - 315 - F: 150
(2 x 70)
250 250 mcm
(2 x 1/0)
300
1)
The details are recommendations. Other designs/laying systems are possible (e.g. according to VDE 0298-4). The
cable cross-sections apply under the following conditions: the use of PVC-insulated copper cables, conductor
temperature < 70°C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
UL approved cables only, fuses and fuse holders must be used.
UL fuse: voltage 500 ... 600 V
3)
Universal-current sensitive earth-leakage circuit breaker
If several devices or cable lengths > 50 m are used, the circuit breaker may respond, depending on the cable type and
switching frequency.
4)
Device with integrated mains choke
c Circuit breaker
d Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
e Fuse
Observe national and regional regulations