Implemented CANopen objects
104 L EDS84DMOTCAN EN 3.0 - 11/2011
I-1801 - TPDO2 communication parameter
Communication parameters for sending process data via TPDO2
For data telegram assignment and description of subindexes, see object I-1800
.
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1801
Name:
TPDO2 communication parameter
Subindex Default setting Setting range (min. value | unit | max. value) Access Data type
0: Highest subindex supported 5 - (read access only) ro U8
1: COB-ID used by TPDO 0x280 + node ID 0 4294967295 rw U32
2: Transmission type 254 0 255 rw U8
3: Inhibit time 0 ms 0 0.1 ms 65535 rw U16
4: Reserved - - (reserved, read or write access results in error
message 0x06090011)
rw U8
5: Event timer 0 ms 0 ms 65535 rw U16
Subindex Meaning Code
0 The value 5 is permanently set.
Max. 5 subindexesare supported.
-
1 TPDO2 identifier
According to the "Predefined Connection Set", the
basic setting is: identifier = 0x280 + node ID
C00354/4
2 TPDO transmission type according to DS301 V4.02
Transmission type
( 52)
C00322/2
3 Minimum time between sending two identical TPDOs
(see DS301 V4.02).
-
5 Cycle time for PDO transmission with transmission type
"254".
C00356/2
C00369