Product description
Variants
MC−CAN2
3
l
11
BA_MC−Card EN 1.0
Technical data
MC−CAN2
Conformity, approval, directive
Conformity
CE EN 61000−6−4
EN 61000−6−2
EMC Directive Class A,
industrial premises
Approval
UR UL 508
CSA C22.2
Process Control Equipment
(File−No. E236341)
Directive
RoHS Products lead−free in accordance with CE
Directive 2011/65/EU
General data and operating conditions
See standard device
Electrical data
Current < 0.2 A at standard device supply voltage of 24 V
Electrical isolation to the
fieldbus
yes
Mechanical data
Mass < 0.1 kg
Communication
Type CAN, ISO011898
Protocol CAN
Topology Line, terminated on both sides with 120 W
Node Master or Slave
Number of nodes max. 63
Max. baud rate 1 MBaud
Bus length ^ CAN communication manual
¸
O Warnings!
Use only together with appropriate cable connectors, provided with screws for
securement and secure connector to avoid loosening.
For use in controlled environment only.
¹
O Warnings!
A utiliser exclusivement avec des connecteurs de câble à vis adaptés. Fixer les
connecteurs pour éviter toute déconnexion.
Destiné uniquement à des zones à environnement contrôlé.