INTERBUS 2MBit/s FOC
Leuze electronic DDLS 200 29
TNT 35/7-24V
Figure 7.1: Connection board of the INTERBUS model
ATTENTION!
Please be sure to observe the installation requirements defined in the INTERBUS stan-
dard EN 50254 and follow the handling and installation specifications for fiber-optic cables
as specified by the manufacturer.
For the FOC guides, use only the large screwed cable gland M20x 1.5.
Do not bend
beyond the specified minimum bending radius given for the FOC type used! Observe the
maximum FOC length!
OUTOUT
WARNWARN
PEPE GNDGND
VinVin
ININ
H1H1H2H2
PEPE GNDGND
VinVin
BSBS
A402AA402A
S1
S3
Off
On
IN
In
Bus
Out
Bus
500K
2M
S2
Out IN
INTERBUS - terminals and switches
FOC socket Function
H1 Receiver fiber-optic cable
H2 Transmitter fiber-optic cable
Switch Function
S2 Position 500k: INTERBUS FOC trans-
mission rate 500kBit/s
Position 2M (default):
INTERBUS FOC trans-
mission rate 2MBit/s
S3 Position In Bus (default):
incoming bus fiber-
optic cable
Position Out Bus: outgoing bus fiber-
optic cable
DDLS200_E.book Seite 29 Mittwoch, 19. Februar 2020 12:22 12