PROFIsafe and PROFINET
Leuze electronic GmbH + Co. KG RSL 420P 121
Input data structure module SYSTEM_DATA
Byte in
non-safe
telegram
Byte in
mod-
ule
Bit Data
type
Signal name Value
‘0‘
Value
‘1‘
Safe Description
6 0 0…15 int16 ALIGNMENT-
H
N Horizontal align-
ment of the spirit
level
-90°…+90°
0.01° display
8 2 0…15 int16 ALIGNMENT-
V
N Vertical alignment
of the spirit level
-90°…+90°
0.01° display
10 4 0…15 int16 SYS-TEMP N Internal system
temperature
0.1°C display
12 6 0…15 int16 VOLTAGE N Applied supply
voltage
0.1V display
11.5.15
Module [M14] – PROTECTIVE_FUNCTION_A_STATUS
• Module ID:0x00000004
• Submodule ID:0x0000000E
The module returns detailed information on the status of protective functionA.
• The module indicates whether the protective field or warning field is free or occupied at a certain angle.
• In addition, the module indicates which field pair is selected for protective function A and whether the
active field pair corresponds to a predefined field pair.
Input data structure module – PROTECTIVE_FUNCTION_A_STATUS
Byte in
non-safe
telegram
Byte in
mod-
ule
Bit Data
type
Signal name Value
‘0‘
Value
‘1‘
Safe Description
14 0 0 Bit A-WF-VIO AS-
SIGNE
D
FREE N Status of active
warning field - pro-
tective functionA
1 Bit A-PF-VIO AS-
SIGNE
D
FREE N Status of active
protective field -
protective function
A
2…3 Bit Reserve
4 Bit A-ACTIVE OFF AC-
TIVE
N Protective func-
tionA active / con-
figured
5…7 Bit Reserve
15 1 0 Bit A-RES-WF OFF AC-
TIVE
N Start/restart active
(warning fieldA)
1 Bit A-RES OFF AC-
TIVE
N Start/restart active
(protective fieldA)
2…7 Bit Reserve